headerdrawing1.jpg (96365 bytes)

Sulphuric Acid on the WebTM Technical Manual DKL Engineering, Inc.

Knowledge for the Sulphuric Acid Industry Line.jpg (1139 bytes)

Sulphuric Acid on the Web

Introduction
General
Equipment Suppliers
Contractor

Instrumentation
Industry News
Maintenance
Acid Traders
Organizations
Fabricators
Conferences

Used Plants
Intellectual Propoerty
Acid Plant Database
Market Information
Library

Technical Manual

Introduction
General

Definitions
Instrumentation
Plant Safety
Metallurgial Processes
Metallurgical
Sulphur Burning
Acid Regeneration
Lead Chamber
Technology
Gas Cleaning
Contact
Strong Acid
Acid Storage
Loading/Unloading

Transportation
Sulphur Systems
Liquid SO2
Boiler Feed Water
Steam Systems

Cooling Water
Effluent Treatment
Utilities
Construction
Maintenance
Inspection
Analytical Procedures
Materials of Construction
Corrosion
Properties
Vendor Data

DKL Engineering, Inc.

Handbook of Sulphuric Acid Manufacturing
Order Form
Preface
Contents
Feedback

Sulphuric Acid Decolourization
Order Form
Preface
Table of Contents

Process Engineering Data Sheets - PEDS
Order Form
Table of Contents

Introduction

Bibliography of Sulphuric Acid Technology
Order Form

Preface
Contents

Sulphuric Acid Plant Specifications
 

Google Search new2.gif (111 bytes)

 

 


Instrumentation - Flow
June 4, 2006

Introduction
Differential Pressure Devices
        Annubars
        Orifice Plates
        Elbow Meters
Magnetic Flow Devices
Mass Flow Meters
        Coriolis Meters
        Thermal Meters
Variable Area Devices
Ultrasonics
        Transit-Time
        Doppler
Instruments
Applications
Associated Links

Introduction

The measurement of flow in an acid plant is important for the control of the process and for troubleshooting problems that may occur.  In some cases, an approximately flow rate is acceptable for control purposes so a relatively inexpensive instrument is acceptable.  In other situations, greater accuracy is required which will require a more sophisticated instrument cost more.  There are a variety of flow measuring devices available but not all are suitable for acid plant service.

Differential Pressure Devices

Flow devices producing a differential pressure signal, have a reputation for accuracy, simplicity and reliability.  Some differential pressure devices are orifice plates, venturi tube, flow nozzles, annubars, wedge flow meters, etc.  The most common types found in sulphuric acid plant application are described.

Annubars

An annubar produces a differential pressure (DP) signal proportional to the square of the flow rate in accordance with Bernoulli's theorem.  This signal has two components; the high pressure (PH) and the low pressure (PL). 

The high pressure is produced by impact of the velocity profile on the sensor.   The velocity profile results in a corresponding impact pressure profile.  Multiple sensing ports located on the front of the sensor, sense the impact pressure profile.  Inside the high pressure chamber, the average velocity pressure is maintained by the proportionality of the sensing port diameters to the chamber cross-sectional area.

The velocity profile continues around the sensor and creates a low pressure profile. The low pressure profile is sensed by ports, located downstream and opposite the high pressure ports.  Working on the same principle as the high pressure side, an average low pressure is maintained in the low pressure chamber.  The resulting differential pressure is transmitted through the instrument head to a differential pressure flow meter.

Orifice Plates

A concentric, sharp-edged orifice plate is the simplest and least expensive of the differential head meters.  The orifice plate constricts the flow of a fluid to produce a differential pressure across the plate.   The result is a high pressure upstream and a low pressure downstream that is proportional to the square of the flow velocity.

The disadvantage of an orifice plate is it usually produces a greater overall pressure loss than other differential pressure devices.  An advantage of this device is that cost does not increase significantly with pipe size.

Elbow Meters

As a fluid passes through a pipe elbow, the pressure at the outside radius of the elbow increases due to centrifugal force.  If pressure taps are located at the outside and inside of the elbow, a reproducible measurement can be made.

Elbow flow meters are inexpensive and do not introduce any obstructions to the flow of liquid.

Magnetic Flow Devices

The operating principle of the magnetic flow tube is based on Faraday's law of electromagnetic induction, which states that a voltage will be induced in a conductor moving through a magnetic field.

Faraday's Law:  E = kBDV

The magnitude of the induced voltage (E) is directly proportional to the velocity of the conductor (V), conductor width (D) and the strength of the magnetic field (B).

Field coils placed on opposite sides of the flow tube generate a magnetic field.   As the conductive process liquid moves through the field with average velocity V, electrodes sense the induced voltage.

The flowmeter must be completely flooded at all times to obtain an accurate measurement of flow.  Installation in vertical pipes where the flow is going up is ideal.  If the flowmeter and piping are drained during shutdowns, this should be specified to the vendor so appropriate measures can be taken to avoid damage to the flowmeter due to overheating.

Mass Flow Meters

True mass flowmeters measure the mass flow directly rather than the volumetric flow and density and then calculate the mass flow from the two measured values.

Coriolis Meters

The Coriolis meter uses an obstructionless U-shaped tube vibrating at its natural frequency as the fluid passes through it.  The tube twists as result of the flowing fluid and the angular movement of the tube created by the vibration.  Sensors measure the amount of twist and this is proportional to the mass flow rate through the pipe.   Coriolis meters operate independent of liquid density, pressure and viscosity.

Thermal Meters

Thermal meters are commonly applied to gas streams only where the transfer of heat to and from them stream is a usual element of the metering process.  Measuring the heat transfer supplies data from which a mass flow rate may be calculated.  Thermal meters operate independent of density, pressure and viscosity.

Variable Area Devices

Variable area devices, more commonly known as rotameters, are typically made from a tapered glass tube that is positioned vertically in the fluid flow.  A flow that is the same size as the base of the glass tube rides upward in relation to the amount of flow.  Because the tube is larger in diameter at the top of the glass than at the bottom, the float resides at the point where the differential pressure between the upper and lower surfaces balance the weight of the float.  In most cases, the flow rate is read directly from a scale inscribed in the flow tube but transmitting rotameters are available.

Ultrasonics

Ultrasonic flow meters utilize sound waves to determine the flow rate of fluids.   Pulses from a piezoelectric transducer travel through a moving fluid at the speed of sound and provide an indication of fluid velocity.   Two different methods are currently employed to establish this velocity measurement; transit-time and Doppler methods.

Ultrasonic meters have several advantages, including freedom from obstructions in the pipe and negligible cost sensitivity with respect to pipe diameter.  However, their performance is sensitive to flow conditions.

Transit-Time

The transit-time method uses two opposing transducers which are mounted at a 45o angle to the direction of flow.  The speed of sound from the upstream transducer to the downstream transducer represent the inherent speed of sound plus a contribution from the fluid velocity.  A simultaneous measurement is taken in the opposite direction which represents the speed of sound minus the fluid velocity.  The difference between these two values is representative of the fluid velocity which is linearly proportional to the flow rate. 

This method works well where the fluid is free of entrained gas or solids which can scatter the sound waves traveling between the transducers.

Doppler

This type of ultrasonic meter uses two transducers mounted in the same case on one side of the pipe.  An ultrasonic sound wave of constant frequency is transmitted into the fluid by one transducer.  Solids or bubbles within the fluid reflect the sound back to the receiver element.  The Doppler principle states that there will be a shift in apparent frequency or wavelength when there is relative motion between transmitter and receiver.  Within the Doppler flow meter, the relative motion of the reflecting bodies suspended within the fluid tends to compress the sound into shorter wave length (high frequency).  This new frequency measured at the receiving element is electronically compared with the transmitted frequency to provide a frequency difference which is directly proportional to the flow velocity in the pipe.  In contrast to the transit-time method, Doppler ultrasonic meters required entrained gases or suspended solids within the flow to function correctly.

Instruments

Instrument Accuracy/Repeatability Installation References Remarks
Annubar ± 1% over a flow turndown of greater than 10 to 1, independent of Reynold's number.
± 0.1% repeatability
7 PDU
3 PDD
(single elbow flow disturbances)
Dieterich Standard Diamond II Annubar Relatively low pressure drop
Orifice Plate ± 2-4% of full scale 10-30 PDU
4-8 PDD
(dependent on flow disturbances and orifice
b ratio)
Relatively high pressure drop
Coriolis ± 0.2% of rate No requirements for upstream of downstream pipe diameters Micro Motion Model D65
Rosemount Technical Data Sheet 3031
Can also be used to measure density of fluid
Magnetic ± 0.5% of rate from 1 to 30 ft/s
± 0.005% from low-flow cut-off to 1.0 ft/s
5 PDU
3 PDD
butterfly valves not recommended immediately upstream or downstream
Rosemount Model 8701 Grounding rings required with lined or not conductive process piping.  Pipe must be running full.
Elbow ± 5-10% of full scale 30 PDU Rosemount Technical Data Sheet 3031 Suitable for liquid flow only.  Typically, there will be insufficient pressure differential generated in gas service.
Thermal ± 2% of full scale No requirements for upstream or downstream pipe diameters Rosemount Technical Data Sheet 3031 Suitable for gas flow measurement only.
Variable Area ± 2% of full scale No requirements for upstream or downstream pipe diameters Rosemount Technical Data Sheet 3031
Ultrasonic Transit-Time: ± 1% of rate
Doppler: ± 3% of rate
5-30 PDU Rosemount Technical Data Sheet 3031

Applications

The following is a list of typical acid plant services for flow meters and the recommended instrument to measure the flow.

Service Instrument Remarks
Sulphuric Acid Magnetic

Use if accurate measurement of flow rate is required.  Advantage is no additional pressure losses are introduced.  The probe type magnetic flow meters should not be used.  These were replaced by the flowtube type.

Orifice

Can be used where accuracy is not important (ie. for alarm or interlock function). Additional pressure drop is introduced to the system.  Material of construction is typically Lewmet (Lewis Pumps).

Ultrasonic

Used primarily as a diagnostic tool for situations where a flowmeter has not been installed. Suitable only for liquid flow measurement.

Elbow

Can be used where accuracy is not important (ie. for alarm or interlock function).  Does not introduce any additional pressure drop to the system.

Liquid Sulphur Wedge Proven reliable and accurate.   Diaphragm seals and a custom steam jacket are required.
Liquid SO2 Coriolis Suitable for use in commerce (i.e. weighing for sales purposes)
Process Gas Annubar Used to measure flow at plant inlet, blower discharge and stack.  Prone to plugging if not maintained properly.
Thermal Should be considered as a replacement for annubars in location where annubars continually plug.
Water Annubar Used where accuracy is required.
Orifice Can be used where accuracy is not important (ie. for alarm or interlock function). Additional pressure drop is introduced to the system.
Rotameters For small flows rates, such as acid dilution or make-up water service.
Steam Orifice Used in saturated or superheated steam service.  Typically, used as part of a multi-point level control for the steam drum level.